Permit: T05CM00896

Parcel: 112017950

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/15/2006 FRAMING Approved IVRS - Inspection :*
03/13/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLOCK TUB WALLS
2) SECURE 4 GANG BOX BEDROOM 2 AND KITCHEN
3) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES WATER HEATER AT ENTRY
4) MAIN SUPPLY ENTRY DUCT RESTRICTED
5) SECURE HOME RUNS
6) FIRE BLOCK MISSING MASTER CLOSET DROPPED CEILING
7) FIRE BLOCK MISSING STAIR WELL
-------------------------------------------------------------------------------------------------
1) UPSTAIRS: SECURE 4 GANG BOX MASTER
2) BLOCK JACUZZI TUB
3) FIRE STOP WATER HEATER FLUE THRU ATTIC AND FURNACE MASTER CLOSET
01/17/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NORTH SOUTH PROPERTY LINE SET BACK NOT PER SITE PLAN
01/05/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) DETAIL 8/86.0 1/2" X 5" LAG BOLTS TO HEADER
PORCH AND 1/2" X 7" LAG BOLTS TO CORBELS IN LIEU OF H2.5