Permit: T05CM00887

Parcel: 11615194B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/12/2006 MECHANICAL - INTERMEDIATE Approved PROVIDE SCREENS IN ROOF VENTS.
EXTEND CONDENSATE DRAINS TO WITHIN 6" OF GRADE. TERMINATE WITH AN ELBOW & NIPPLE.
REMOVE SCREWS FROM DRYER VENTS. USE RIVETS IF NECESSARY. NO TAPE OUTDOORS. EXTEND WATER HEATER VENTS 2' ABOVE COMBUSTION AIR INTAKE ON ROOF. FURNACE VENTS ARE ABANDONED. PROVIDE MIN 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR. PROVIDE A HIGH COMBUSTION AIR VENT. PROVIDE PLATE STRAPS IN LAUNDRY ROOMS.