Permit: T05CM00887

Parcel: 11615194B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM00887

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/01/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUND BAR STILL REQUIRED FOR UNIT #106, UNIT 110 NOT READY
2) OK 101, 102, 105, 109 AND 99
06/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) USE LISTED GROUND BARS IN SUB PANELS FOR GROUND TERMINATIONS , ALL ON BLUE WIRE NUT NOT APPROVED. 2) CIRCUIT BREAKERS MUST ALL BE SAME MANUF AS PANEL.
06/22/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* UNITS 101, 102 ONLY. PLEASE PROVIDE THE ARC FAULT CIRCUIT AND BREAKER OR HAVE ENGINEER ISSUE INFORMATION OR REMEDY. THIS APPLIES TO BOTH BEDROOMS.