Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05CM00887
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
03/01/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. SES 1&2&3 SUPPORT USERS UNDER ROOF ONCE WITHIN 3' 2. SES #1 USE BRASS CLAMP ON GRID ROD 3. SES #1 WIRE NOT GROUND IN SERVICE - #10'S 4. SES #3 RE TORQUE NEUTRAL ON SERVICE - CK SES 1 & 2 5. SUPPORT #4 GROUNDS TO SER TO WALLS |
|
02/16/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PROVIDE CORRECT FEEDER/UNIT CALCULATIONS INCLUDE ALL EQUIPMENT |
|
02/10/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SEE REPORT FOR ACTIVITY #T05CM02511 |
|
02/01/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXISTING SYSTEM TO INDIVIDUAL PANEL DID NOT HAVE AN EQUIPMENT GROUND, PLANS SHOW IT DID, NOW INDIVIDUAL EQUIPMENT GROUND WIRES RUN TO PANELS INDIVIDUALLY MUST BE A PART OF CABLE SYSTEM 2. CABLE SEAT TO ENTER ENCLOSURE 3. FEEDERS CANNOT BE SPLICED IN WALLS |
|
01/30/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*SERVICE NOT READY |