Permit: T05CM00887

Parcel: 11615194B

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/02/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/01/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. SES 1&2&3 SUPPORT USERS UNDER ROOF ONCE WITHIN 3'
2. SES #1 USE BRASS CLAMP ON GRID ROD
3. SES #1 WIRE NOT GROUND IN SERVICE - #10'S
4. SES #3 RE TORQUE NEUTRAL ON SERVICE - CK SES 1 & 2
5. SUPPORT #4 GROUNDS TO SER TO WALLS
02/16/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PROVIDE CORRECT FEEDER/UNIT CALCULATIONS INCLUDE ALL EQUIPMENT
02/10/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
1. SEE REPORT FOR ACTIVITY #T05CM02511
02/01/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXISTING SYSTEM TO INDIVIDUAL PANEL DID NOT HAVE AN EQUIPMENT GROUND, PLANS SHOW IT DID, NOW INDIVIDUAL EQUIPMENT GROUND WIRES RUN TO PANELS INDIVIDUALLY
MUST BE A PART OF CABLE SYSTEM
2. CABLE SEAT TO ENTER ENCLOSURE
3. FEEDERS CANNOT BE SPLICED IN WALLS
01/30/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*SERVICE NOT READY