Permit: T05CM00884

Parcel: 11615194B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM00884

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/29/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/09/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
RICK 870-8863
IMC 2003 - SEC. 403.3.4 VENTILATION SYSTEMS SHALL BE BALANCED BY AND APPROVED METHOD AS REQUIRED BY
SEC. 403
THESE DUCT SYSTEMS CANNOT BE BALANCED WITH THESE GRILLS LOCATED ON SUPPLY TOPS.
03/07/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
NOT READY!
1. GAS LINES PROGRESSING!
2. WHY AREN'T SUPPLY REGISTERS BEING USED. ALL SUPPLY TAPS HAVE A STAMPED RETURN AIR 60GH GRILL OK FOR RETURN AIR OPENINGS.