Permit: T05CM00884

Parcel: 11615194B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/10/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK WALLS IN UNITS-CHECK INSIDE NEW 6 PACK SERVICE
10/18/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*DO NOT USE WATER SYSTEM AS AN EQUIP GROUND TO GROUND SUB PANELS.RUN EQUIP GROUND TO SERVICE AS INDICATED ON PLAN. UNITS TO BE METERED INDIVIDUALLY, BOND WATER PIPING EACH UNIT/
ISOLATE NEUTRALS & GROUNDS IN SUB PANELS
COMPLETE CABLE TERMINATIONS AT ALL UNITS.
OUTSIDE ENTRY LIGHTS MUST HAVE PRO?? J-BOX FOR TERMINATION