Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* / 1) LABEL SERVICE FOR UNITS AND MAINTAIN CLEARANCES 110.26. OK FINAL. | |
| 05/20/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/19/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SWITCHES TO BE GROUNDED, ALSO TIGHTEN GROUND TERMINALS 2) PROTECT SEAL TITE FROM SHARP METAL EDGES 3) BOND DISCONNECT ENCLOSURE 4) ONLY ONE CONDUCTOR PER LUG 5) TIGHTEN LOOSE FITTINGS 6) CONDUCTOR AMPACITY TO BE AS PER 334.80 FOR NM CABLES (#8) 7) TIGHTEN CONNECTORS FOR HOOD CORDS |