Permit: T05CM00867

Parcel: 14113017A


Addresses:

9348 E RITA RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM00867

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/06/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK TO CLEAR FUEL & TESTING POWER ( IMAGING X RAY)
08/28/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO TILE EXCEPT AS NOTED
2) FINISH ITEMS 3 AND 4 OF PREVIOUS INSPECTION
08/25/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) MANUFACTURERS FIXTURE CLIPS TO BE EFFECTIVE 410.16
2) FINISH ATTACHING SUPPORT WIRES
3) SUPPORT CONDUITS TO STRUT RACK
4) WHERE ARE EXIT LIGHTS ?
5) NOTE: VDV CABELING TO BE INSTALLED PER 725.6 AND 800.6
08/22/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*