Permit: T05CM00862

Parcel: 140383870

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/11/2005 FRAMING Approved IVRS - Inspection :*
1) RE-INSPECT
06/28/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) SHEARWALL 6 REQUIRES EDGE NAILING AT 4" ON CENTER
2) NO DWV WATER TEST
3) BLOCK DEFUSER BOLTS 3 SIDES
4) SHEARWALL NOT CLIPPED PER 10/DT1
5) RED HEAD ANCHOR BOLTS LOOSE
6) STUCCO LATH NOT COMPLETE
7) RE-ROUTE CONDENSATES
8) SHIM HEADERS LEVEL
9) SHEARWALL 7 REQUIRES 5/8" ANCHOR BOLTS AT 24" ON CENTER
10) 3/4" RED HEAD WEDGE ANCHORS NOT ALLOWED WITHIN 7 1/2" OF SLAB EDGE
11) MISSING RANGE HOOD
12) WHERE IS A/C COPPER
13) MISSING HOLDOWN BOLTS
14) STOPPED INSPECTION