Permit: T05CM00857

Parcel: 140377990

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
09/28/2005 SHEET ROCK NAILING Approved IVRS - Inspection :*
09/26/2005 SHEET ROCK NAILING Denied IVRS - Inspection :
The drywall is not nailed per code.| 175*
1) 5/8" TYPE X DRYWALL REQUIRED GARAGE CEILING UNDER OCCUPIED SPACE PER NOTE 56 PAGE 1.1 AND IRC R309.2 AND WALLS SUPPORTING SECOND FLOOR
2) HOUSE OK TO TAPE NOT GARAGE