Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2005 | FRAMING | Approved | ||
| 08/08/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/29/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) F5A, F1A TRUSSES CUT. PROVIDE ENGINEERING REPORT APPROVED BY CITY OF TUCSON 2) F2 HEADER NOT BEARING ON HANGER 3) HOLDOWN HTT16 MISSING |
|
| 07/22/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LSL NOT NAILED PER PLAN 2) NORTH P-1 REQUIRES ANCHOR BOLTS AT 16" ON CENTER 3) F2 HEADER NOT BEARING ON HANGER 4) TRUSS HANGERS MISSING NAILS 5) DUCTS RESTRICTED BY PLUMBING DINING ROOM AND POWDER ROOM 6) SEAL FLOOR PENETRATIONS 7) POWDER ROOM PLUMBING LEAK 8) FIRE STOP ENTRY 9) REPLACE DAMAGED HANGER BY STAIRS 10) DOOR BELL TRANSFORMER NOT ALLOWED IN ATTIC IRC 4202.3 11) NAIL PROTECT PLUMBING AND WIRES 12) FIRE STOP S.E. BEDROOM FROM GARAGE #3 13) PLUMBING OUT OF WALL |