Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/15/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL PLUG IN OPENING A/C DISCONNECT INSIDE HOUSE 2) ELECTRIC BOX UTILITY ROOM NEEDS COVER 3) NEED MANUFACTURER SPECS ON MATERIAL USED FOR INTERIOR AND EXTERIOR 4) NEED FOR INSULATION FILL EXTERIOR WALLS 5) KITCHEN OUTLETS TO BE GFCI ISLAND 6) MAXIMUM 30 AMP BREAKER A/C CIRCUIT 7) POST PERMANENT ADDRESS ON HOUSE VISIBLE FROM STREET 8) POST PERMANENT ADDRESS AT STREET ALSO 9) MINIMUM 3" CLEARANCE UNDER BOTTOM OF COPPER H20 HEATER POP OFF TERMINATION 10) NEED INSULATION CERTIFICATE |