Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS SUBJECT TO BUILDING INSPECTOR |
|
| 09/12/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PANEL NOT ALLOWED IN CLOSET 2) MAINTAIN FIREWALL SEPERATION 3) PROTECT NM CABLE AS PER 300.4 ALSO DATA 4) BOXES OTHER THAN SINGLE GANG TO UTILITIES BOX CLAMPS TO BE SECURED TO BOX-FILL UNUSED OPENINGS IN BOXES 5) SUPPORT NM CABLE WITHIN 12" AND 8' ON HORIZONALS 6) A BOX MAY BE NEEDED FOR BATH LIGHT 7) BRING JUNCTION BOX BROWN CEILING SURFACE 8) FINISH UNIT #449 |