Permit: T05CM00839

Parcel: 133163020

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM00839

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2006 FRAMING Approved IVRS - Inspection :*
01/03/2006 FRAMING Partial Approval IVRS - Inspection :*
1) NEED TO SEE BEAM TO COLUMN CONNECTIONS AT BALCONY
12/28/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*NO ACCESS
11/17/2005 FRAMING Partial Approval IVRS - Inspection :*FIREWALL SHOULD EXTEND THE LENGTH & HEIGHTS WALL WHERE THERE IN AN ADJACENT UNIT
11/16/2005 FRAMING Partial Approval IVRS - Inspection :*NEED TO FIRE CAULK W/U.L RATED SYSTEM @ PENETRATIONS
09/12/2005 FRAMING Partial Approval IVRS - Inspection :*
1) NO STRUCTURAL DAMAGE INSIDE FROM FIRE
2) ENGINEER MUST EVALUATE AND DESIGN REPAIR FOR BOTTOM NOTCHED AND OVER DRILLED FLOOR RAFTERS UNIT #348
3) FIREBLOCKING REQUIRED
08/25/2005 FRAMING Not ready for Inspection IVRS - Inspection :*