Permit: T05CM00837

Parcel: 112061240

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
04/20/2005 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
1) REVISION VERIFIED
04/05/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) OK TO BACKFILL PENDING REVISION OF 4" ABS TO 3"
04/04/2005 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS MUST HAVE STAMPED APPROVAL DATED FROM CITY OF TUCSON PLAN REVIEW FOR ANY REVISION
2) PLAN CALLS FOR 4" ABS
3) 3" INSTALLED. REVISE PLAN TO SHOW 3" OR BUILD TO PLAN
4) AN INSPECTION WAS NEEDED AT HCS TO SEWER
03/31/2005 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROOF OF SEWER CONNECTION AT STREET
2) NOT OK TO COVER TRENCH UP TO STREET
3) PLAN CALLS FOR 4" ABS
4) 3" INSTALLED/REVISE PLAN TO SHOW 3" OR BUILD TO PLAN