Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DATA PLATE ON PKG. HT PUMPS MARKED NO AUX. HEAT STRIPS. UNITS FUSED IN CORRECTLY -- TOO LARGE! CHECK/CORRECT - LEAVE PROPERLY FUSED! THIS MECHANICAL CONTR. SHOULD BE CHECKING TO MAKE SURE HIS EQUIP. IS CORRECTLY CONNECTED. |