Permit: T05CM00826

Parcel: 10808001B


Addresses:

5850 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECTIONS NOT MADE FROM PREVIOUS INSPECTION
02/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*DRINKING FOUNTAIN OUTLET NEEDS TO BE ACCESSIBLE
J BOX IN JANITOR CLOSET NEEDS TO BE ACCESSIBLE
NEED GFI PROTECTION FOR ALL BATH RECEPTACLES BRANCH CKY RACEWAYS ARE OVERFILLED
BRACH CKT'S NEED DERATED PER 310.15 (A)
PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
IDENTIFY A.C DISCONNECTS AND PROVIDE IN MSE COVERS FOR GFI'D & ONLY 1 GROUND UNDER LUG UNLESS LISTED.
MAKE SURE EMERGENCY LIGHTING IS PER PLANS AND WIRED TO LIGHTING CKT IN THE AREA IT SERVES
PROVIDE ACCESS TO MAIN J BOX