Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTIONS NOT MADE FROM PREVIOUS INSPECTION |
|
| 02/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*DRINKING FOUNTAIN OUTLET NEEDS TO BE ACCESSIBLE J BOX IN JANITOR CLOSET NEEDS TO BE ACCESSIBLE NEED GFI PROTECTION FOR ALL BATH RECEPTACLES BRANCH CKY RACEWAYS ARE OVERFILLED BRACH CKT'S NEED DERATED PER 310.15 (A) PANEL DIRECTORY NOT CORRECTLY IDENTIFIED IDENTIFY A.C DISCONNECTS AND PROVIDE IN MSE COVERS FOR GFI'D & ONLY 1 GROUND UNDER LUG UNLESS LISTED. MAKE SURE EMERGENCY LIGHTING IS PER PLANS AND WIRED TO LIGHTING CKT IN THE AREA IT SERVES PROVIDE ACCESS TO MAIN J BOX |