Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2005 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 06/15/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* OK WALLS AND HARD CEILING. 1) NEED A STAMP ON M/C LETTER. |
| 06/13/2005 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* 1) VDV CABLING TO BE SUPPORTED AS PER CODES 725.6. 2) M/C CABLE TO BE CENTERED IN ST?D CHANNEL OR PROTECTED 300.4 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES, FIXTURES OR FITTINGS. 4) IF USING BACKF TO BACK MINI'S PLEASE PROPERLY SUPPORT. 5) TIGHTEN LOOSE FITTINGS. 6) PLEASE PROTECT PVC AT BASE PLATE. 7) CONTRACTOR TO FURNISH LETTER FOR M/C USAGE. |
| 03/30/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* OK 2-3/4" PVC UNDER SLAB |