Permit: T05CM00816

Parcel: 129130730


Addresses:

807 E 31ST ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/21/2007 FRAMING Approved IVRS - Inspection :*
02/20/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REVISE PLAN TO REFLECT EXISTING DIMENSION IN BATHROOM AND HAVE IT APPROVED BY DSD
2) PROTECT ELECTRICAL WIRES AND PLUMBING WHERE INDICATED
12/29/2006 FRAMING Partial Approval IVRS - Inspection :*
1) FINAL FRAMING APPROVAL PENDING INTERMEDIATES
2) POST ADDRESS CLEARLY VISIBLE FROM STREET
12/26/2006 FRAMING Partial Approval IVRS - Inspection :*
1) NOTE: PROVIDE REINFORCED ALL TRUSSES ACCORDING WITH CALC'S. PROVIDE STUDS ON BEARING WALL 16" ON CENTER, NAILS ON EACH HOLE H2.5 AND CLIPS WALLS. PROVIDE CORRECT VENTS FOR ATTIC VENTILATION VENTS=12 X 12
12/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE PRESENT FOR ACCESS 7:30
PLEASE RECALL
08/28/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUBMIT AS BUILD TRUSSES TO DEV. SER. CTR FOR APPROVAL
2) EAST EXTERIOR BEARING WALL STUDS SHALL BE AT 16" ON CENTER
3) HEADER REQUIRED OVER ALL BEARING OPENING HAVE D.S.C. DETERMINE SIZE REQUIRED
4) ALL ABOVE NOT COMPLIED WITH
05/15/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST REPLACE ALL ROTTED ROOF RAFTERS AND SHEATHING
2) NEED DETAILS ON TRUSSES-RAFTERS, ETC...
3) HEADERS NOT TO CODE
4) TIGHTEN ALL NUTS ON PLATE BOLTS
5) INSTALL PALTE BOLTS MAXIMUM 48" APART AND WITHIN 12" END OF EACH BOTTOM PLATE
6) TRUSS MEMBER GANG NAILS APPEAR DAMAGED-LOOSE ?
7) BLOCK ALL HORIZONTAL JOINTS EXTERIOR OSB
8) INSTALL H2.5'S BOTTOM PLATE TO STUD; STUD TO TOP PLATE: TOP PLATE TO TRUSS OR RAFTER
9) IT APPEARS ENTIRE ROOF STRUCTURE UNSAFE NOT TO MINIMUM STANDARD. RE-SUBMIT ENGINEERED DETAILS ON ALL ROOF STRUCTURE COMPONENTS TO BE IN COMPLIANCE WITH CODE
10) STOPPED INSPECTION