Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM00815
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2005 | FRAMING | Approved | IVRS - Inspection :* | |
05/19/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER LINES NEED 12" CLEARANCE FROM CAN LIGHTS 2) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR 3) HTT 16 MISSING EPOXY BOLT 4) PATIO HANGERS MISSING NAILS AND USE CORRECT NAILS PER MANUFACTURER 5) OVERSPAN NORTH WEST WALL 6) DWV TEST NOT HOLDING 7) W/H CHASE NOT FRAMED 8) BLOWN FIRE BLOCK AT SOUTH WEST BEDROOM 9) CAN LIGHT TOUCHING OSB UPSTAIRS HALL PROVIDE MANUFACTURER INSTRUCTIONS FOR CLEARANCE FROM COMBUSTIBLES 10) DBL TOP PLATE AT BALLOON WALL NOT STAGGERED 11) STOPPED INSPECTION |