Permit: T05CM00800

Parcel: 110121000


Addresses:

5166 E GLENN ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/06/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) DWV WATER TEST IS OK
2) OVERHEAD WATER DISTRIBUTION IS OK
3) ALL CORRECTIONS HABE BEEN MADE
05/26/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL VENT PIPING PER APPROVED PLAN M 3.2
2) INSTALL HANGERS ON ALL PIPING AT CHANGES OF DIRECTION AND AT APPROPRIATE INTERVALS
3) CALL IN 3005 FOR INSPECTION
4) OK TO INSULATE WATER PIPING
05/24/2005 PLUMBING - INTERMEDIATE Cancelled CANCELLED PER SUPERINTENDENT RON
05/24/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*