Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE PROVIDE A LETTER FOR DELETION OF FRONT GFI. OK TEMP C OF O SUBJECT TO DETERMINATION OF INSPECTIONS MANAGER. | |
| 07/05/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20. 2) CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 200.7 3) INSTALL ALL DEVICES. 4) MAINTAIN WORKING CLEARANCE WATER HEATER DISCONNECT. 5) EIT LIGHTING NOT FULLY FUNCTIONAL. 6) FINISH LIGHTING AT SUB PANEL. 7) THIS HAS BEEN AN UNNECESSARY INSPECTION AS DISCUSSED_ A REFEE HAS BEEN ASSESED. |