Permit: T05CM00742

Parcel: 134234230


Addresses:

6444 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM00742

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
AIR BALANCE IS OK
OK FOR FINAL
01/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DUCT DETECTORS MUST BE ACCESSIBLE & PROVIDE AUDIBLE & VISIBLE ALARMS.
12/28/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE COVERS OVER CANVAS CONNECTORS
2) FINISH MARKING DATA PLATES
3) PROVIDE FRESH AIR INTAKES
4) PROVIDE SLEEPERS
5) PERMANENTLY IDENTIFY UNITS ON ROOF
6) PLANS REQUIRE DUCT SMOKE DETECTORS IN 5 TON UNITS. PROVIDE LETTER FROM ENGINEER IF DELETING
7) CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP
8) PROVIDE SPECS FOR CONDENSATE PUMP
12/22/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
NO ACCESS TO ROOF
PLEASE RESCHEDULE SOMETIME AFTER TUESDAY