Permit: T05CM00742

Parcel: 134234230


Addresses:

6444 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM00742

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2007 PLUMBING - INTERMEDIATE Approved
09/12/2006 PLUMBING - INTERMEDIATE Partial Approval AT RESTROOMS: DCW INSTALLED PER REVISION 3 OF 9/6/06
HAVE REVISED PLANS APPROVED.
OTHER CORRECTION NOT YET COMPLETED
09/06/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER PIPING NOT INSTALLED PER PLAN.
2. SHALL PROVIDE TEST ON WASTE & VENT THRU ROOF.
3. CLOSET FLANGE SHALL BE SECURED, 1/4" ABOVE FINISH FLOOR + WITH DUTCHMEN IN RISER PIPE FLUSH WITH TOP OF STOOL RING WITH VIEWING PRIOR TO SETTING STOOLS.
07/18/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WATER TEST FROM EXISTING 3" BUILDING DRAIN FOR RESTROOMS PER PLAN THRU REVENT TO 2' ABOVE 2ND LEVEL OK.
2. WILL NEED TEST ON VENT THRU ROOF.
3. PLAN HAS BEEN APPROVED IN ERROR. PUBLIC USE LAVS REQUIRE THAT WATER HEATER NOT BE SOLE CONTROL OF HOT WATER TEMPERATURE. PROVIDE TEMPERING WITH REVISED APPROVED PLAN FOR THIS.
4. NEED TO SEE PERM. CAPS ON ALL DEMO WASTE & VENT PIPING IN WALL & UNDER SLAB LOCATION.