Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00729
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR ECO SP # 100 COMMERCIAL | |
03/21/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* BLD LOCKED RECALL INSPE. |
|
03/18/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES MC CABLE MUST BE SUPPORTED PER NEC. WITHIN 12: EACH TERMINATION AND AT 6" INTERVALS, MUST BE INDEPENDENTLY SUPPORTED TO STRUCTURE. DO NOT USE CEILING GRID WIRES INTENDED TO SUPPORT GRID CEILING. |
|
03/17/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE LADDER TO INSP. WORK ABOVE CEILING GRID, REMOVE TILES AROUND POWER POLE, TRACK LTG, PANEL A |