Permit: T05CM00729

Parcel: 12411021E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR ECO SP # 100 COMMERCIAL
03/21/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920* BLD LOCKED RECALL INSPE.
03/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES MC CABLE MUST BE SUPPORTED PER NEC. WITHIN 12: EACH TERMINATION AND AT 6" INTERVALS, MUST BE INDEPENDENTLY SUPPORTED TO STRUCTURE. DO NOT USE CEILING GRID WIRES INTENDED TO SUPPORT GRID CEILING.
03/17/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* PROVIDE LADDER TO INSP. WORK ABOVE CEILING GRID, REMOVE TILES AROUND POWER POLE, TRACK LTG, PANEL A