Inspection History Details
Permit: T05CM00724
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/16/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* WATER TEST & VENT THRU ROOF OK. H20 PIPING AIR TEST OK | |
| 03/14/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT CONNECT A DRAIN INTO A VENT OF A VENT INTO A DRAIN. SHALL CONNECT DRAIN BELOW VENT UNDER SLAB. 2) RE TEST THE SYSTEM. |
|
| 03/11/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LAVATORY DIRTY ARM MAX SIZE IS 1 1/2" MAX TRAP SIZE FOR LAVATORIES IS ONE PIPE SIZE. LARGER THAN THE OUTLET OF THE FIXTURE. OUTLET OF LAVATORY IS 1 1/4. THE TRAP SHALL BE THE SAME SIZE AS THE DRAIN SERVED. |