Permit: T05CM00698

Parcel: 11301146Y


Addresses:

3601 N CAMPBELL AV


Inspection Status: Approved

Inspection History: MECHANICAL - HOOD SYSTEMS

Permit Number - T05CM00698

Inspection Description - MECHANICAL - HOOD SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2005 MECHANICAL - HOOD SYSTEMS Approved PER MECH FINAL
05/26/2005 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) WALK IN BOX CONDENSOR ON ROOF-NEEDS WEATHER ENCLOSURE. CONDENSATE DRAIN LINE-PROVIDE TRAP OVER FLOW SINK
2) WATER HEATER TERMINATE B-1 VENT 3 FT ABOVE EVAP COOLER AND GAS FLEX LINE 3/8" X 5 FT RATED 53,200 ? FT
3) INPUT BTU WT. HTR. 75,100 BTUH
05/10/2005 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :* EXHAUST DUCTS, FIRE MASTER WRAP.
05/03/2005 MECHANICAL - HOOD SYSTEMS Partial Approval OK TO SET TILES IN DINING AREA. EXHAUST DUCT OK. OK TO WRAP. FOLLOW DETAIL #1 ON HOOD SECTION. SHT M2.