Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM00698
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK 2) OK FOR C OF O PENDING ANY OTHER INSPECTION |
|
05/24/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CLEAN-OUT BEHIND WATER CLOSET REQUIRES 18" CLEARANCE IN FRONT 2) ICE MACHINE IN FRONT HAS BACKFLOW PROTECTION, WHY DOESN'T THE MACHINE IN THE KITCHEN HAVE ONE ? 3) KITCHEN ICE MACHINE-DRAINS MAY NOT BE COMBINED, MUST BE SUPPORTED, MUST HAVE AIR GAP 4) I MIGHT BE INCLNED TO APPROVE DRAINS FROM BEVERAGE DISPENSOR/ICE MAKER IN FRONT IF THE DRAINS HAD THE PROPER AIR GAP 5) MUST HAVE SIGN IDENTIFYING ANSUL VALVE LOCATION ABOVE ? CEILING 6) HAVE ALL BACKFLOW CERTS AVAILABLE |