Permit: T05CM00691

Parcel: 14024061B


Addresses:

1445 E WIEDING RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/09/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/03/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
09/21/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CRIMPED END WRONG DIRECTION WHERE VENT CONNECTS TO UNIT HEATERS.
- PLANS REQUIRE UNIONS & HARD PIPIE GAS TO UNIT HEATERS.
- PROVIDE T-STATS.
- PERMANENTLY IDENTIFY ALL EQUIPMENT.
- REPAIR DAMAGED VENT CAP ON FURNACE.
- INSTALL EXHAUST FAN FOR RESTROOMS.
- CONNECT WATER TO EVAP. COOLERS.