Permit: T05CM00687

Parcel: 140383470

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/08/2005 FRAMING Approved IVRS - Inspection :*
06/06/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) LATH NOT STAPLED
2) GARAGE SW 7 NOT NAILED PER PLAN
3) WIRING OUT OF WALL CAVITY
4) STOPPED INSPECTION
5) HOUSE NOT COMPLETE ENOUGHT TO INSPECT
06/02/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) LATH NOT STAPLED
2) GARAGE SHEARWALL 7 NOT NAILED PER PLAN 3" ON CENTER
3) SHEARWALL 7 REQUIRES A35 CLIPS AT 8" ON CENTER
4) SHEARWALL 7 REQUIRES ANCHOR BOLTS AT 24" ON CENTER
5) SHIM HEADER
6) REPLACE BEARING STUDS NOTCHED MORE THAN 25 PERCENT
7) A/C AND 220 TO FAR APART
8) SEAL ALL VAPOR BARRIER PENETRATIONS
9) FIRESTOP REQUIRES 2 LAYERS OF 1/2" OSB
10) MANY ANCHOR BOLTS LOOSE
11) BEDROOM 2 REQUIRES 2-2 X 10 HEADER
12) STOPPED INSPECTION TO MANY ITEMS