Permit: T05CM00658

Parcel: 131010120


Addresses:

1255 S BEVERLY AV


Inspection Status: Partial Approval

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T05CM00658

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/06/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PIPE STANDS OK IN VAULT. PLEASE ASK ENGINEER ABOUT SPACING OF STANDS; HAS HE TAKEN FLEX CONNECTOR INTO CONSIDERATION
01/10/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) NORTH WALL CENTER SECTION OK TO CLOSE AND POUR
01/04/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) OK TO CLSOE AND POUR MIDDLE SECTIONS OF VALVE VAULT
2) SUMP PIT PER ?K1 IS LACKING CONTINUITY OF HORIZONTALS. I HAVE MET WITH SPECIAL INSPECTOR AND HE MAY CONFIRM CORRECTION
3) OK TO PLACE CONCRETE WHEN SP. INSP. CONFIRMS CORRECTION
12/23/2005 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*EAST WALL WITH 10' TURN BACK
OK TO CLOSE AND PLACE CONCRETE
12/09/2005 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) WEST WALL PROVIDE 4 EXTRA BARS A SOUTH OPENING
2) PROVIDE PROPER CLEARANCE #10 VERTS ON SOUTH SIDE OF NORTH VALVE
3) OK TO POUR WHEN SPECIAL INSPECTOR CONFIRMS
11/18/2005 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*BOTTOM OF VALVE VAULT OK
10/18/2005 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*CALL WHEN FOOTINGS FOR VAULT ARE READY TO BE INSPECTED.