Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM00649
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
06/08/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND METAL BOX F/STAIR LIGHT 2) NAIL PROTECT ELECTRIC WITHIN 1 1/4 FROM EDGE OF STUD 3) SEE LAST INSPECTIONS |
|
06/06/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL ITEMS NOT COMPLETED 2) STOPPED INSPECTION |
|
05/26/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIREBLOCK MISSING AT STAIR STRINGER 2) A/C PLATFORM AND CAT RUN UNSAFE 3) SECURE WATER LINE BEHIND MASTER TUB 4) STOPPED INSPECTION |
|
05/20/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIREBLOCK CAHSE AT GARAGE 2) REPAIR SHEAR AT GARAGE 3) GARAGE GFCI ROMEX MUST HAVE 1/4" OF SHEATHING INTO BOX 4) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR 5) NAIL PROTECT ROMEX AT LOFT EAST WALL, B/R NORTH WEST 6) REPAIR SHEAR PANEL 7) NAIL PROTECT ROMEX AT KITCHEN 8) SECURE ROMEX AT HALL BATH WITHIN 8" FROM B 9) LEAK AT UPSTAIRS BATH 10) B-2 TRUSS ABOVE LAUNDRY, PROVIDE APPROVED ENGINEER REPAIR 11) REPAIR DBL TOP PLATE SOUTH WEST WALL NOTCHED MORE THAN 25 PERCENT 12) ZERO-GAS PRESSSURE TEST |