Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2006 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
| 04/25/2006 | ELECTRIC - OUTDOOR LIGHTING | Not ready for Inspection | IVRS - Inspection :* 1. NEED REJECTION PINS AT MAIN DISCONNECT. 2. CANNOT STACK LUGS 3. PREVENT OBJECTIONABLE CURRENTS ON GROUNDING CONDUCTORS 250.6 4. LABEL DISCONNECT AND PANEL ON OUTSIDE OF COVER 5. PLEASE VERIFY DERATING OF CONDUCTORS PER 310.15 6. CONNECT ALL CONDUCTORS 7. BOND CONDUITS AROUND WHERE CROSSING CONCENTRICS |