Permit: T05CM00625

Parcel: 12106226A


Addresses:

5502 E PIMA ST #100

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/03/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/25/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO TILE
2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON-COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 314.20 (METAL NOT APPROVED)
3) PERMANENT CIRCUIT DIRECTORIES ARE NEEDED
05/16/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) MC CABLE TO BE INDEPENDENTLY SUPPORTED 300.11. 2) VDV CABLE TO BE SUPPORTED AS PER 725.6. 3) SUPPORT BOXES ON CONDUITS ABOVE WALLS. 4) USE SUPPORT WIRES (2) FOR ALL FIXTURES.