Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/25/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO TILE 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON-COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 314.20 (METAL NOT APPROVED) 3) PERMANENT CIRCUIT DIRECTORIES ARE NEEDED |
|
| 05/16/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) MC CABLE TO BE INDEPENDENTLY SUPPORTED 300.11. 2) VDV CABLE TO BE SUPPORTED AS PER 725.6. 3) SUPPORT BOXES ON CONDUITS ABOVE WALLS. 4) USE SUPPORT WIRES (2) FOR ALL FIXTURES. |