Permit: T05CM00618

Parcel: 126130200


Addresses:

4590 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM00618

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL C OF O
09/09/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CLEAN ALL RUST OFF OF BLOCK IRON EXHAUST DUCT ON THE ROOF AND PAINT DUCT
2) PROVIDE LISTING FOR THE CANVAS CONNECTION USED ON THE EXHAUST FAN
3) MUST BE RATED FOR HIGH TEMP AND APPROVED FOR USE ON A TYPE I SYSTEM
4) PROVIDE A COVER OVER CANVAS CONNECTOR
09/08/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE PROVIDE THE INSTALL INSTRUCTIONS FOR THE VENT PIPE USED ON THE WATER HEATER. THERE MAYBE TO MANY OFF SETS EXCEEDING 60 DEGREE. PROVIDE MINIMUM 1" CLEARANCE FROM INSULATION AND WOOD. PROVIDE ACCESS TO ROOF