Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM00618

Parcel: 126130200


Addresses:

4590 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T05CM00618

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2005 MECHANICAL - HOODS Approved
07/07/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :* INSPECTED ( ?? LAYER OF FIRE WRAP OK TO PROCEED WITH 2ND LAYER)
07/01/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) REMOVE ALL OF THE WIRE FROM THE FIRE WRAP MATERIAL AND FOLLOW THE MANUFACTURERS INSTRUCTIONS
2) YOU CAN USE FILAMENT TAPE TO TEMPORARILY HOLD THE 1ST LAYER OF WRAP SPACED THE SAME AS THE BANDING REQUIREMENTS
3) DO NOT USE FOIL TAPE ON THE JOINTS AND SEAMS
4) CANNOT CHECK OVERLAP REQUIREMENTS. LEAVE INSTALL INSTRUCTIONS ON JOB SITE
06/30/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :* INSPECTION ON GREASE DUCTS. OK TO PROCEED WITH FIRE WRAP.
06/23/2005 MECHANICAL - HOODS Cancelled IVRS - RI canceled