Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T05CM00618
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2005 | MECHANICAL - HOODS | Approved | ||
07/07/2005 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* INSPECTED ( ?? LAYER OF FIRE WRAP OK TO PROCEED WITH 2ND LAYER) | |
07/01/2005 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) REMOVE ALL OF THE WIRE FROM THE FIRE WRAP MATERIAL AND FOLLOW THE MANUFACTURERS INSTRUCTIONS 2) YOU CAN USE FILAMENT TAPE TO TEMPORARILY HOLD THE 1ST LAYER OF WRAP SPACED THE SAME AS THE BANDING REQUIREMENTS 3) DO NOT USE FOIL TAPE ON THE JOINTS AND SEAMS 4) CANNOT CHECK OVERLAP REQUIREMENTS. LEAVE INSTALL INSTRUCTIONS ON JOB SITE |
|
06/30/2005 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* INSPECTION ON GREASE DUCTS. OK TO PROCEED WITH FIRE WRAP. | |
06/23/2005 | MECHANICAL - HOODS | Cancelled | IVRS - RI canceled |