Permit: T05CM00610

Parcel: 13414001K

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) RECEIVED LETTER ON LIGHTING CHANGES AND PLENIUM WIRING
06/07/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) EXISTING VDV CABLEING TO BE AS PER 725/2 7 725.6, 800.2 800.6 2) FILL UNUSED OPENING IN BOXES. 3) LIGHTING NOT RELOCATED AS PER PLAN. PLEASE PROVIDE A LETTER OR INSTALL AS PER PLANS. 4) SUPPORT WIRES NEEDED FOR BOXES OF EXIT LIGHTING. 5) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING. 320.14. ALSO ?? IS NOT AN APPROVED SPACER. 6) PLEASE VERIFY PLENIUM RATEING ON VDV CABELING. 7) CHECK SERVICE NEXT TIME.