Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS OR PERMIT 2) WORK NOT ACCOMPLISHED |
|
| 07/29/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OK TO INSULATE 2) DBL STUDS WITH HTT16 AT P-3 SHEAR NOT NAILED AT 3" ON CENTER |
|
| 07/28/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1. GARAGE P3 SHEAR HTT 16 IN WRONG LOCATION 2. NO GAS PRESSURE TEST 3. NO DWV WATER TEST 4. NO GAS BOND 5. FILL ALL ROUND NAIL HOLES IN HANGERS 6. T&P LINE OUT OF WALL MUST BE 6" ABOVE SLAB OUTSIDE 7. LAUNDRY PLUMBING OUT OF WALL |
|
| 07/27/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |