Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2005 | ROOF NAILING | Approved | IVRS - Inspection :* | |
| 04/14/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/12/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) T9 TRUSSES MISSING TRUSS BRACING 2) X BRACE THREE TRUSSES AT ENDS AND EVERY 25 LF 3) T6 TRUSSES MISSING BRACING 4) T7 TRUSSES MISSING BRACING 5) STRAP NON OVER LAPPING DBL TOP PLATES 6) SHEAR WALL 4 NOT NAILED PER PLAN 7) 2/D2 NOT NAILED THRU ROOF SHEATHING 8) 2/D3 NOT COMPLIED WITH AT SHEARWALL 4 9) 10A/D2 CLIPS MISSING 10) 1/D3 MUST USE 8D NAILS THRU ROOF SHEATHING |