Permit: T05CM00577

Parcel: 119410340


Addresses:

1906 W PROBASCO DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/04/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/03/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/02/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/20/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REVISE PLANS TO SHOW CHANGES
2) FIRE BLOCKING MISSING THROUGHOUT
3) INT. BEARING WALL MISSING AND CUT NAILS
4) NAIL PROTECT ELEC THROUGHOUT
5) SHIM HEADERS WHERE NEEDED
6) REMOVE TAPE FROM DRYER VENT ELBOWS
7) NO TEST ON DWV'S
8) REMOVE 90'S FROM VFR'S
9) SECURE ROMEX WITHIN 8" FROM BOX
10) FIRE BLOCK CHASE AT GARAGE
STOPPED INSP