Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL C OF O |
|
| 04/11/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RELOCATE DUCT SMOKE DETECTOR AS NEEDED. SENSING TUBE MUST COVER AT LEAST 85% OF AIR FLOW. |
|
| 07/05/2005 | MECHANICAL - FINAL | Cancelled | CANCELLED PER RON G & J DEVELOPMENT 419-6030 | |
| 07/05/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY | |
| 06/30/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* POWER SUPPLY NOT ADEQUATE FOR 40 AMP HEAT STRIP & 45.1 AMP A/C UNIT. UNIT REQUIRES SEPARATE POWER SUPPLY FOR EACH. PERMANENTLY IDENTIFY A/C UNIT W/SUITE NUMBER. PROVIDE SCREENS IN EXHAUST FAN T-?? OK FOR TEMP C OF O. |
|
| 06/29/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED ACCESS TO ROOF TOP |