Permit: T05CM00575

Parcel: 110121000

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/19/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL C OF O
04/11/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RELOCATE DUCT SMOKE DETECTOR AS NEEDED.
SENSING TUBE MUST COVER AT LEAST 85% OF AIR FLOW.
07/05/2005 MECHANICAL - FINAL Cancelled CANCELLED PER RON G & J DEVELOPMENT 419-6030
07/05/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :* NOT READY
06/30/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* POWER SUPPLY NOT ADEQUATE FOR 40 AMP HEAT STRIP & 45.1 AMP A/C UNIT. UNIT REQUIRES SEPARATE POWER SUPPLY FOR EACH. PERMANENTLY IDENTIFY A/C UNIT W/SUITE NUMBER. PROVIDE SCREENS IN EXHAUST FAN T-?? OK FOR TEMP C OF O.
06/29/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :* NEED ACCESS TO ROOF TOP