Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE VERIFY LISTING LABEL OFR HAMILTON EXAM TABLE 2) INSTALL A PERMANENT CIRCUIT DIRECTORY 3) BREAKER TO BE LISTED FOR USE BY MANUFACTURER 4) DO YOU NEED EXIT LIGHTING? 5) FINISH PREVIOUS ITEMS 6) TIGHTEN LOOSE FITTINGS 7) SUPPORT SEAL TITE 8) NEED PLANS ON SITE |
|
| 07/05/2005 | ELECTRIC - FINAL | Cancelled | CANCELLED PER RON G & J DEVELOPMENT 419-6030 | |
| 07/05/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/30/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1) CORRECTLY IDENTIFY CONDUCTOR COLORS 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20. OK TEMP C OF O SUBJECT TO DETERMINATION OF INSPECTIONS MA?? | |
| 06/22/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |