Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK TO TILE |
|
| 06/10/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FINISH ELECTRIC AND PREVIOUS INSPECTION ITEMS |
|
| 05/04/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*CANCELLED BY OFFICE | |
| 05/03/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FILL UNUSED OPENINGS IN BOXES. 2) SUPPORT WIRE NEEDED FOR EXHAUST FAN. 3) ATTACH FIXTURES TO GRID AND SUPPORT WITH WIRES. NOTE CANS TO HAVE HOUSINGS BROUGHT FLUSH IN TILES FOR TRIMS |