Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T05CM00567
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2005 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
04/26/2005 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL HOLES IN EQUIPMENT 2) PHYSICALLY PROTECT WIRING FROM 480 V DISCONNECT TO TRANS 3) CHANGE OUT WIRING FROM 480V DISCONNECT TO TRANS 4) CLEAN WIRING TERMINATIONS AT 480V DISCONNECT, ALSO AT THE TRANSFORMER TERMINALS 5) CORRECT THE MULTIPLE GROUNDING AT BASE OF TRANSFORMER. PROVIDE SEPERATE TERMINATIONS WHERE GROUND ELECTRODE CONDUCTOR ?-SEPERATE STRANDED AND SOLID CONDUCTORS 6) REPAIR SO CORD COMING OUT OF PANEL, RESET TEARS AT FITTING AND REPAIR SO CORD ON BOARD |