Permit: T05CM00567

Parcel: 13612833C

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T05CM00567

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2005 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
04/26/2005 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL ALL HOLES IN EQUIPMENT
2) PHYSICALLY PROTECT WIRING FROM 480 V DISCONNECT TO TRANS
3) CHANGE OUT WIRING FROM 480V DISCONNECT TO TRANS
4) CLEAN WIRING TERMINATIONS AT 480V DISCONNECT, ALSO AT THE TRANSFORMER TERMINALS
5) CORRECT THE MULTIPLE GROUNDING AT BASE OF TRANSFORMER. PROVIDE SEPERATE TERMINATIONS WHERE GROUND ELECTRODE CONDUCTOR ?-SEPERATE STRANDED AND SOLID CONDUCTORS
6) REPAIR SO CORD COMING OUT OF PANEL, RESET TEARS AT FITTING AND REPAIR SO CORD ON BOARD