Permit: T05CM00558

Parcel: 136312540

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/20/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
1) NEED HTT22 FRONT OF HOUSE NEAR S.W. CORNER AT FRAME INSPECTION
2) ADD STUD EACH SIDE OF STOVE VENT
3) ADD BLOCKING AS NEEDED TO CARRY LOAD OF GIRDER TRUSSES THRU TO THE FOUNDATION