Permit: T05CM00549

Parcel: 140378000

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/04/2005 FRAMING Approved IVRS - Inspection :*
08/02/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 2 X BLOCKING PER 3A/SD2 OVER LAUNDRY HEADER
2) LIVING ROOM P-2 SHEARWALL REQUIRES ANCHOR BOLTS AT 16" ON CENTER
3) LEAK AT TUB
4) NO GAS TEST
5) NAIL PROTECT RANGE CABLE AT TOP PLATE
6) 1" CLEARANCE REQUIRED W/H VENT TO COMBUSTIBLES AT HALL BATH
7) SECURE SHOWER ANGLE 90
08/01/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER JOE