Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2005 | REINFORCED MASONRY PRE-GROUT | Approved | ||
| 07/07/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BOND BEAM PER PLAN |
|
| 06/23/2005 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 1ST 48" LIFT |
|
| 06/16/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OBTAIN NEW SET OF APPROVED PLANS AND RECALL 2) CANNOT USE THESE TORN UP PLANS |
|
| 06/08/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERTICAL REBAR MUST BE TIED INTO VERTICAL REBAR SET IN CONCRETE IN SLAB 2) REMOVE BLOCK; EPOXY REBAR IN CONCRETE AT ALL DOOR AND WINDOW OPENINGS, CORNERS, JAMS; MAXIMUM 48" OF RUN; RECALL BEFORE RE-LAYING BLOCK TO CHECK EPOXIED REBAR |
|