Permit: T05CM00539

Parcel: 112031730


Addresses:

2818 E MCKENZIE ST

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/22/2005 REINFORCED MASONRY PRE-GROUT Approved
07/07/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL BOND BEAM PER PLAN
06/23/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 1ST 48" LIFT
06/16/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OBTAIN NEW SET OF APPROVED PLANS AND RECALL
2) CANNOT USE THESE TORN UP PLANS
06/08/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERTICAL REBAR MUST BE TIED INTO VERTICAL REBAR SET IN CONCRETE IN SLAB
2) REMOVE BLOCK; EPOXY REBAR IN CONCRETE AT ALL DOOR AND WINDOW OPENINGS, CORNERS, JAMS; MAXIMUM 48" OF RUN; RECALL BEFORE RE-LAYING BLOCK TO CHECK EPOXIED REBAR
06/06/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO VERTS IN SLAB AT WINDOW AND DOOR OPENINGS