Permit: T05CM00539

Parcel: 112031730


Addresses:

2818 E MCKENZIE ST

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Date Description Inspector Results Comments
05/10/2005 BUILDING PRE-SLAB Approved IVRS - Inspection :*
05/06/2005 BUILDING PRE-SLAB Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAINTAIN MINIMUM 3" CLEARANCE REBAR TO DIRT
2) PLAN CALLS FOR 21.3 ADDITION (OVER 25' AS BUILT)
3) WRAP ALL PLASTIC PLUMBING PIPE THAT WILL BE IN CONTACT WITH CONCRETE
4) MOVE GALVANIZED H20 PIPE FROM UNDER SLAB
5) STOPPED INSPECTION-INCOMPLETE