Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/07/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PROVIDE TRUSS REPAIR PER ITEM 8-JULY 6, 2005 2) OK TO DRY WALL ALL BUT S.W. BR CLOSET |
|
| 07/06/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT WIRES. 2. SHIM F? HEADER. 3. TOP STAIR THREAD TOO SHORT. 10" REQUIRED. 4. SECOND FLOOR SHEAR WALL BOTTOM PLATE NOT NAILED TO FLOOR PER PLAN. 6) PROVIDE SHEAR WALL STUD NAILER WEST LAUNDRY. 7) NAIL PROTET PLUMBING AT LAUNDRY. 8) DAMAGED TRUSS PLUMBER DRILLED HOLE IN TRUSS PROVIDE CITY APPROVED ENGINEERING REPAIR |
|
| 06/30/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 2) SHEARWALL P-3 HOLDOWN WRONG LOCATION REQUIRES 13'-11" SHEARWALL 3) P-3 SHEARWALL NOT ANCHORED PER PLAN 4) HALL 1/2 BATH NOT CONNECTED 5) DRYWALL OVERSPAN 1/2 BATH 6) NO GAS PRESSURE TEST 7) NO DWV TEST 8) STOPPED INSPECTION-TO MANY ITEMS |