Permit: T05CM00532

Parcel: 140376720


Addresses:

6923 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/22/2005 FRAMING Approved IVRS - Inspection :*
07/07/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PROVIDE TRUSS REPAIR PER ITEM 8-JULY 6, 2005
2) OK TO DRY WALL ALL BUT S.W. BR CLOSET
07/06/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NAIL PROTECT WIRES. 2. SHIM F? HEADER. 3. TOP STAIR THREAD TOO SHORT. 10" REQUIRED. 4. SECOND FLOOR SHEAR WALL BOTTOM PLATE NOT NAILED TO FLOOR PER PLAN. 6) PROVIDE SHEAR WALL STUD NAILER WEST LAUNDRY. 7) NAIL PROTET PLUMBING AT LAUNDRY. 8) DAMAGED TRUSS PLUMBER DRILLED HOLE IN TRUSS PROVIDE CITY APPROVED ENGINEERING REPAIR
06/30/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
2) SHEARWALL P-3 HOLDOWN WRONG LOCATION REQUIRES 13'-11" SHEARWALL
3) P-3 SHEARWALL NOT ANCHORED PER PLAN
4) HALL 1/2 BATH NOT CONNECTED
5) DRYWALL OVERSPAN 1/2 BATH
6) NO GAS PRESSURE TEST
7) NO DWV TEST
8) STOPPED INSPECTION-TO MANY ITEMS