Inspection History Details
Permit: T05CM00531
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WAITING ON DBL WALL FOR B-VENT FURNACE |
|
| 08/31/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTE # 2, #3 2) SINGLE WALL NOT ALLOWED IN ATTIC FAV B-VENT 3) REST OF HOUSE OK |
|
| 08/29/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DISCONNECT MISSING FUSES 2) GRADING NOT COMPLETE REAR 3) SERVICE GFCI NOT WITHIN 25' FT OF CONDENSATOR 4) ARC FAULT TESTER INDICATES SHARED NEAUTRALS 5) FAV PAN HAS BLOWN INSULATION IN IT 6) PROVIDE ORIGINAL PERMIT CARD (HARD COPY) 7) REST OF HOUSE OK |
|
| 08/26/2005 | BUILDING - FINAL | Denied | 1) FAN AT LAUNDRY NOT WORKING 2) A/C UNIT NOT HOOKED UP |